Overfill Prevention Valves/Assemblies - A1100 Testable Overfill Prevention System
Emco’s A1100-T Testable Overfill Prevention Valve allows for quick and easy testing without removing the valve from the tank riser. Simply use the A0081-1100 Testing Rod to depress the test button installed on the valve, and shine a light inside the valve - if the reflective tape is visible, the valve is operational. The testable A1100-T OPV uses the same proven technology as the A1100 OPV Series. Assemblies are factory welded and 100% factory tested. Bottom tube screws to top tube/ valve assembly - No Epoxy. This saves time in the field and assures a vapor tight assembly to meet the EPA 40 CFR Part 63 requirements.
Body: Aluminum
Drop Tubes: Aluminum (anodized available)
Floats: HDPE
Seals: Viton®
Viton® is a registered trademark of The Chemours Company
Model No. Description Purpose
493192 Valve to Tube Rivet Assembly Kit Contains material required to install valve onto drop tube
493734S Riser Collar Kit Contains material required to add a riser collar onto the top tube assembly
493734SXL Riser Collar Kit Extended, 10.7" Contains material required to add an extended riser collar onto the top tube assembly
49373SXXL Riser Collar Kit Extended, 20.7" Contains material required to add an extended riser collar onto the top tube assembly
566675 Drill Fixture, Steel Aligns holes for drilling to ensure a vapor-tight seal
572719 Drill Fixture, Plastic Aligns holes for drilling to ensure a vapor-tight seal
A0081-1100 Testing Rod
Depresses test button and linkage. Shine a light down into the interior of the valve (alternatively, snap a photo). If the reflective tape is visible, the valve is OK
Filter Options
A1100 Testable
Model No. | Application | Nominal Tank Dia. | Max. Burial Depth | Upper Tube Length (A) | Lower Tube Length (B) | Max. Overall Length (C) | Annodized |
---|---|---|---|---|---|---|---|
A1100-010T | Valve Only | N/A | N/A | N/A | N/A | N/A | |
A1100-085TP | Coaxial Self-Sealing* | 8 ft. | 5.4 ft. | 65" | 82" | 162" | |
A1100-086TP | Coaxial Self-Sealing* | 10 ft. | 5.3 ft. | 65" | 94" | 174" | |
A1100-087TP | Coaxial Self-Sealing* | 12 ft. | 5.1 ft. | 65" | 120" | 200" | |
A1100EVR-055T | Dual Point | 8 ft. | 6.0 ft. | 70" | 82" | 167" | |
A1100EVR-055TCF | Dual Point | 8 ft. | 6.0 ft. | 70" | 82" | 167" | ✔ |
A1100EVR-056T | Dual Point | 10 ft. | 7.0 ft. | 82" | 92" | 191" | |
A1100EVR-056TCF | Dual Point | 10 ft. | 7.0 ft. | 82" | 92" | 191" | ✔ |
A1100EVR-057T | Dual Point | 12 ft. | 6.8 ft. | 82" | 120" | 217" | |
A1100EVR-057TCF | Dual Point | 12 ft. | 6.8 ft. | 82" | 120" | 217" | ✔ |
Model No. | Application | Nominal Tank Dia. | Max. Burial Depth | Upper Tube Length (A) | Lower Tube Length (B) | Max. Overall Length (C) | Annodized |
The A1100 Overfill Prevention Valve is not recommended for tanks under 6.5’ in diameter.
Maximum burial depth assumes 95% shut-off and 6” clearance between top of drop tube and inside bottom of containment manhole lid.
*includes Adapter and Cap